Parallel Inverters
Behind-the-meter sites with more than one inverter wire them in parallel: one master inverter and one or more slaves. Flip models the whole stack as one device: the master. This page covers what to commission, how to combine values across inverters, and how to handle commands.
Why only the master
The master is the control point for the stack:
- It takes the VPP instructions. The master accepts the operating mode and power setpoint and shares the work out across the slaves. Slaves follow the master and are not controlled on their own.
- It measures the site. The grid meter (CT) is normally wired to the master, so grid import/export is measured once, for the whole home.
- A VPP dispatches the site, not the inverter. Programs enroll a home and expect one stated capacity and one power response from it.
If you register each inverter as its own device, Flip sees several batteries at one site. Each is dispatched separately, the site is counted more than once, and the slaves receive commands they cannot act on. So register only the master, and report values for the whole stack under it.
Commissioning
Send one entry in devices for the site, using the master's id and serial_number. Do not send the slaves.
Fill the device attributes for the whole stack:
| Field | How to fill it |
|---|---|
battery_capacity_wh | Sum across all inverters' batteries |
inverter_ac_max_discharge_w / inverter_ac_max_charge_w | Sum across inverters |
battery_dc_max_discharge_w / battery_dc_max_charge_w | Sum across batteries |
site_export_limit_w | Single value: the export limit at the meter applies to the whole site, so don't sum it |
round_trip_efficiency | Single value for the stack |
capabilities.* | Single value for the site (for example, has_solar is true if any inverter has solar) |
Telemetry
Report one reading per interval under the master's device_id, combining the inverters as follows. Field names are from POST /v1/telemetry/BATTERY_COUNTER. On POST /v1/telemetry/BATTERY, apply the same rules to the matching fields: sum battery_total_energy_charge_wh, battery_total_energy_discharge_wh and solar_total_energy_wh; report grid_total_energy_wh and home_total_energy_wh once for the site; and use the master's start_time and duration_s.
| Field | How to combine |
|---|---|
battery_energy_charge_wh_counter, battery_energy_discharge_wh_counter, solar_energy_wh_counter | Sum |
battery_last_power_charge_w, battery_last_power_discharge_w, solar_last_power_w | Sum |
battery_last_stored_energy_wh, battery_last_capacity_energy_wh | Sum |
battery_last_state_of_charge_percentage | Weighted by capacity: total stored energy ÷ total capacity × 100 |
battery_last_state_of_health_percentage | Weighted by capacity |
grid_*, home_* (power and counters) | Site total, measured once at the meter. Don't add up copies of the same meter reading from each inverter |
battery_last_backup_reserve_percentage, last_mode, device_settings, last_is_grid_online, is_weather_alarm_active | The master's value |
last_is_online | Whether the master is reachable and controllable |
last_has_active_fault | true if any inverter has an active fault |
faults | Faults from all inverters, combined into one list |
timestamp | The master's reading time |
State of charge: weight it, don't average it
Batteries in a stack often differ in size, so a plain average of each inverter's state of charge is wrong.
| Capacity | Stored | State of charge | |
|---|---|---|---|
| Inverter A | 20,000 Wh | 10,000 Wh | 50% |
| Inverter B | 10,000 Wh | 2,000 Wh | 20% |
| Stack | 30,000 Wh | 12,000 Wh | 40% (12,000 ÷ 30,000) |
A plain average would report 35% and understate the energy available.
Keep counters steady when a slave drops out
If a slave misses a reading, keep adding its last known counter values to the sum. If you leave it out instead, the summed counter drops, and a drop in a lifetime counter reads as a reset.
Control
Commands arrive for the master device, and they apply to the whole stack:
setpoint_wis the target for the whole stack, not for each inverter. Pass it to the master and let the master share it across the slaves.backup_reserve_percentageis the reserve for the whole stack.- Acknowledge commands for the master only, not for each inverter, via
PATCH /v1/command/{commandId}.
See Battery Modes for what each mode should do.
Already registered the slaves?
If a site was commissioned with one device per inverter, contact us and we'll remove the extra devices. Then update the master with the stack totals above, and send all telemetry under the master's device_id. When you start summing, add only each slave's increase from that point on, so the master's counters don't jump by the slaves' lifetime totals.
Checklist
- Commission one device per site: the master
- Sum capacity and power limits across the stack; send export limit, efficiency and capabilities once
- Sum energy counters, battery and solar power, stored energy and capacity
- Report state of charge as total stored energy ÷ total capacity
- Report grid and home values once, for the site
- Keep summed counters steady when a slave misses a reading
- Treat command setpoints as stack totals, and acknowledge for the master only